Factory Supply Power Supply Online LCD Display Transformer Base 1-20kVA Low Frequency Double Conversion UPS for Chemical Industry
Having a sound small business credit score, outstanding after-sales services and modern manufacturing facilities, we’ve got earned an fantastic reputation among our buyers across the globe for Factory Supply Power Supply Online LCD Display Transformer Base 1-20kVA Low Frequency Double Conversion UPS for Chemical Industry, We’ll offer most effective top quality, quite possibly the most sector aggressive value, for each new and old customers with all the most excellent green services.
Having a sound small business credit score, outstanding after-sales services and modern manufacturing facilities, we’ve got earned an fantastic reputation among our buyers across the globe for China UPS and DC Power Supply, So We also continuously function. we, focuse on high quality, and are conscious of the importance of environmental protection, most of the merchandise are pollution-free, environmentally friendly items, reuse on the solution. We have Updated our catalog, which introduces our organization. n detail and covers the primary objects we deliver at present, You may also visit our web-site, which involves our most recent product line. We look forward to reactivating our company connection.
Description
Brand: Banatton
Place of origin: China
Type: online UPS
Model Number: BNT900-31 10~20KVA
Display: LED
Phase: Three Phase
Waveform: Pure sine wave
Transfer time: 0ms
Power factor: 0.99
Capacity: 10KVA 15KVA 20KVA
Protection: short-circuit, over voltages, reverse connection protection
OEM/ODM: Yes
Supply Ability: 5000 Piece/Pieces per Month
Packaging: Carton or wooden box package or as you requested
Features
Little Hint
1. In the warranty period the machine has a problem, please contact the sales staff, we will be responsible for customer service.
2. Exceed the warranty period, improper operation and man-made damage, we will still give help and support, we will provide spare parts at a cost price.
3. According to the customer’s needs, we can provide unconventional, but the cost may be slightly higher than the traditional machine.
Applications
Data processing center, The host system, Computer servers, Medical, Traffic, Electricity, IT, Industrial and other industries.
Factory Production Line
Packaging
Having a sound small business credit score, outstanding after-sales services and modern manufacturing facilities, we’ve got earned an fantastic reputation among our buyers across the globe for Factory Supply Power Supply Online LCD Display Transformer Base 1-20kVA Low Frequency Double Conversion UPS for Chemical Industry, We’ll offer most effective top quality, quite possibly the most sector aggressive value, for each new and old customers with all the most excellent green services.
Factory Supply China UPS and DC Power Supply, So We also continuously function. we, focuse on high quality, and are conscious of the importance of environmental protection, most of the merchandise are pollution-free, environmentally friendly items, reuse on the solution. We have Updated our catalog, which introduces our organization. n detail and covers the primary objects we deliver at present, You may also visit our web-site, which involves our most recent product line. We look forward to reactivating our company connection.
MODEL |
BNT9010S-31 |
BNT9010H-31 |
BNT9015S-31 |
BNT9015H-31 |
BNT9020H-31 |
Capacity |
10KVA/8KW |
15KVA/12KW |
20KVA/16KW | ||
INPUT | |||||
Rated voltage |
380/400/415Vac (3 phases+N) |
||||
Voltage range |
190~ 520Vac (3 phases)@ 50% load |
||||
305 ~ 520Vac (3 phases) @100% load |
|||||
Frequency |
46~54Hz or 56~64Hz (auto-sense) |
||||
Power factor |
≥ 0.99 @100% load |
||||
Bypass voltage range |
-25% ~ +15% (settable) |
||||
OUTPUT | |||||
Voltage |
220/230/240Vac |
||||
Voltage regulation |
± 1% |
||||
Frequency |
50 or 60±0.2Hz (battery mode) |
||||
Waveform |
Sinusoidal |
||||
Crest factor |
3:1(max) |
||||
Harmonic distortion |
≤ 3% (linear load); ≤ 5% (non-linear load) |
||||
Transfer time |
Mains mode to battery mode: 0 ms |
||||
Inverter mode to bypass mode: 0 ms (typical) |
|||||
Overload capability |
105% ~ 125%: transfer to bypass in 3min |
||||
125% ~ 150%: transfer to bypass in 30s |
|||||
> 150%: transfer to bypass in 1s |
|||||
EFFICIENCY | |||||
Mains mode |
≥ 92% |
||||
Battery mode |
≥ 91% |
||||
ECO mode |
≥ 98% |
||||
BATTERY | |||||
DC voltage |
192V |
192~240V |
192V |
192~240V |
192~240V |
Inbuilt battery |
16×9Ah |
/ |
16×9Ah |
/ |
/ |
Charging current (max.) |
/ |
4A(standard) |
/ |
4A(standard) |
4A(standard) |
Recharge time |
8h |
||||
ALARMS | |||||
Utility failure |
4s per beep |
||||
Low battery |
1s per beep |
||||
Overload |
1s twice beep |
||||
UPS fault |
Long beep |
||||
COMMUNICATIONS | |||||
RS232 (standard) / USB (optional) |
Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / Windows® 7 / 8 / 10 |
||||
SNMP (optional) |
Power management from SNMP manager and web browser |
||||
OTHERS | |||||
Operating temperature |
0 ~ 40℃ |
||||
Relative Humidity |
0 ~ 90% RH (non-condensing) |
||||
Noise level |
≤ 60 dB (1m) |
||||
Dimensions (D×W×H) (mm) |
442×190×318 |
575×190×318 |
|||
Net weight (kg) |
66 |
15 |
67 |